Heavy Oil Dowtherm Boiler

Heavy Oil Dowtherm Boiler

Heavy Oil Dowtherm Boiler Model DO-50H Description Heavy Oil Dowtherm Boiler Model DO-50H 1. We provide the dowtherm boiler with vertical and horizontal models, vertical type reduced space and horizontal type is easy to maintenance, however, they are equally efficient in performance. 2. Special flue designed can reducing exhaust temperature, to reach combustion and heat transfer of the highest efficiency, and no danger of local overheating. 3. For the excellent design of the heating pipe and heat-absorbing disc, the circulating speed of Dowtherm oil is average, its pressure drop is very low, Dowtherm oil does not have local overheating, and lengthen its life.   Feature Heavy Oil Dowtherm Boiler Model DO-50H Alarm of liquid level Insufficient. Alarm of Circulation Pump Fail. Dowtherm oil
Call Seller for Quote
Model: DO-50H
Company Information
Name : ZU HOW INDUSTRY CO., LTD.
Contact : ซือ หาว อินดัสทรี ไทยแลนด์
Tel : Please login.

Heavy Oil Dowtherm Boiler Model DO-50H

Description Heavy Oil Dowtherm Boiler Model DO-50H

1. We provide the dowtherm boiler with vertical and horizontal models, vertical type reduced space and horizontal type is easy to maintenance, however, they are equally efficient in performance.
2. Special flue designed can reducing exhaust temperature, to reach combustion and heat transfer of the highest efficiency, and no danger of local overheating.
3. For the excellent design of the heating pipe and heat-absorbing disc, the circulating speed of Dowtherm oil is average, its pressure drop is very low, Dowtherm oil does not have local overheating, and lengthen its life.

 

Feature Heavy Oil Dowtherm Boiler Model DO-50H

  • Alarm of liquid level Insufficient.
  • Alarm of Circulation Pump Fail.
  • Dowtherm oil temperature limit.
  • Chimney temperature limit.
  • Pressure differential controller:make sure oil flowing.
  • Safety valve:system valve limit.

 

Specification Heavy Oil Dowtherm Boiler Model DO-50H

Type Unit DO-15H DO-20H DO-30H DO-50H DO-60H DO-80H DO-100H DO-125H DO-150H DO-175H DO-200H
Type - Vertical Horizontal
Heat output ×10000kcal/hr 15 20 30 50 60 80 100 125 150 175 200
Max. Working temperature 300 300 300 300 300 300 300 300 300 300 300
Design pressure kg/cm2   7 7 7 7 7 7 7 7 7 7 7
Boiler dowtherm oil content L 150 200 300 550 600 850 1050 1300 1600 2000 2100
Fuel consumption Heavy oil L/h 19.1 25.4 38.1 63.5 76.2 101.6 127.0 158.8 190.6 222.3 254.1
Burner type Heavy oil - H30 H40 H60 H100 H120 H150 H200 H250 H300 H350 H400
Electrical Power capacity Heavy oil Kw 4.6 4.6 6.8 10.3 14.1 19.3 24.9 31.0 42.2 46.0 57.2
Circulation pump HP 5 5 7.5 10 15 20 25 30 40 40 50
Boiler scales Length mm 1570 1570 1810 2260 2260 2260 2260 2260 4000 4200 4500
Width mm 1240 1240 1600 1750 1850 1850 1850 1850 1850 2200 2200
Heigth mm 1950 2130 2250 2620 2700 2800 3000 3200 2200 2550 2550
Thermal oil dia - 2" 2" 2" 2-1/2" 3" 4" 4" 4" 5" 5" 5"
Diameter of chimney mm 200 200 200 290 330 360 360 400 400 485 485
Approximate weight kg 2200 2500 3000 3600 4200 4900 5600 6300 7000 7800 8600